GE Multilink Uncontrolled Resource Consumption
Summary
| CVE | CVE-2014-5418 |
|---|---|
| State | PUBLISHED |
| Assigner | icscert |
| Source Priority | CVE Program / NVD first with legacy fallback |
| Published | 2015-01-17 02:59:01 UTC |
| Updated | 2026-05-06 22:30:45 UTC |
| Description | GE Multilink ML800, ML1200, ML1600, and ML2400 switches with firmware 4.2.1 and earlier and Multilink ML810, ML3000, and ML3100 switches with firmware 5.2.0 and earlier allow remote attackers to cause a denial of service (resource consumption or reboot) via crafted packets. |
Risk And Classification
Primary CVSS: v2.0 7.8 from [email protected]
AV:N/AC:L/Au:N/C:N/I:N/A:C
Problem Types: CWE-400 | CWE-399 | CWE-400 CWE-400
| Version | Source | Type | Score | Severity | Vector |
|---|---|---|---|---|---|
| 2.0 | [email protected] | Primary | 7.8 | AV:N/AC:L/Au:N/C:N/I:N/A:C | |
| 2.0 | [email protected] | Secondary | 5 | AV:N/AC:L/Au:N/C:N/I:N/A:P | |
| 2.0 | CNA | CVSS | 5 | AV:N/AC:L/Au:N/C:N/I:N/A:P |
CVSS v2.0 Breakdown
AV:N/AC:L/Au:N/C:N/I:N/A:C
NVD Known Affected Configurations (CPE 2.3)
| Type | Vendor | Product | Version | Update | Edition | Language |
|---|---|---|---|---|---|---|
| Hardware | Ge | Multilink Ml1200 | - | All | All | All |
| Operating System | Ge | Multilink Ml1200 Firmware | All | All | All | All |
| Hardware | Ge | Multilink Ml1600 | - | All | All | All |
| Operating System | Ge | Multilink Ml1600 Firmware | All | All | All | All |
| Hardware | Ge | Multilink Ml2400 | - | All | All | All |
| Operating System | Ge | Multilink Ml2400 Firmware | All | All | All | All |
| Hardware | Ge | Multilink Ml3000 | All | All | All | All |
| Operating System | Ge | Multilink Ml3000 Firmware | All | All | All | All |
| Hardware | Ge | Multilink Ml3100 | All | All | All | All |
| Operating System | Ge | Multilink Ml3100 Firmware | All | All | All | All |
| Hardware | Ge | Multilink Ml800 | - | All | All | All |
| Operating System | Ge | Multilink Ml800 Firmware | All | All | All | All |
| Hardware | Ge | Multilink Ml810 | - | All | All | All |
| Operating System | Ge | Multilink Ml810 Firmware | All | All | All | All |
Vendor Declared Affected Products
| Source | Vendor | Product | Version | Platforms |
|---|---|---|---|---|
| CNA | GE | Multilink ML800/1200/1600/2400 | affected 4.2.1 custom | Not specified |
| CNA | GE | ML810/3000/3100 Series Switch | affected 5.2.0 custom | Not specified |
References
| Reference | Source | Link | Tags |
|---|---|---|---|
| www.gedigitalenergy.com/products/support/multilink/MLSB1214.pdf | af854a3a-2127-422b-91ae-364da2661108 | www.gedigitalenergy.com | Vendor Advisory |
| github.com/cisagov/CSAF/blob/develop/csaf_files/OT/white/2015/icsa-15-01... | [email protected] | github.com | |
| GE Multilink Switch Vulnerabilities | ICS-CERT | af854a3a-2127-422b-91ae-364da2661108 | ics-cert.us-cert.gov | Third Party Advisory, US Government Resource |
| www.cisa.gov/news-events/ics-advisories/icsa-15-013-04a | [email protected] | www.cisa.gov | |
| CVE Program record | CVE.ORG | www.cve.org | canonical |
| NVD vulnerability detail | NVD | nvd.nist.gov | canonical, analysis |
Vendor Comments And Credit
Discovery Credit
CNA: Eireann Leverett of IOActive (en)
Additional Advisory Data
Solutions
CNA: GE recommends users update switch firmware to the latest published version to resolve these vulnerabilities. The new firmware will enable new keys to be calculated and exchanged, resolve the slow data transfer and potential denial of service, and prevent the identified cross-site scripting vulnerabilities. The latest firmware is Version 5.3.2 for the ML800, ML1200, ML1600 and ML2400 and Version 5.3.2-3K for the ML810, ML3000, and ML3100. This firmware is available through the “Resources/Software” link in the product web sites at http://www.gedigitalenergy.com . This firmware is also available through the EnerVista Launchpad device management tool. GE recommends updating the switch over a serial connection to prevent an attacker from capturing the new key. Please refer to the GE advisory for specific information on how to install the firmware and change RSA key. The GE advisory is available at: https://www.gedigitalenergy.com/products/support/multilink/MLSB0415.pdf
Legacy QID Mappings
- 591284 General Electric Multilink Switch Rivest Shamir Adleman (RSA) Private Key and Denial of Service (DoS) Multiple Vulnerabilities (ICSA-15-013-04A)