CVE-2022-24039
Published on: Not Yet Published
Last Modified on: 06/30/2023 06:48:00 PM UTC
Certain versions of Desigo Pxc4 from Siemens contain the following vulnerability:
A vulnerability has been identified in Desigo PXC4 (All versions < V02.20.142.10-10884), Desigo PXC5 (All versions < V02.20.142.10-10884). The “addCell” JavaScript function fails to properly sanitize user-controllable input before including it into the generated XML body of the XLS report document, such that it is possible to inject arbitrary content (e.g., XML tags) into the generated file. An attacker with restricted privileges, by poisoning any of the content used to generate XLS reports, could be able to leverage the application to deliver malicious files against higher-privileged users and obtain Remote Code Execution (RCE) against the administrator’s workstation.
- CVE-2022-24039 has been assigned by
productc[email protected] to track the vulnerability - currently rated as CRITICAL severity.
- Affected Vendor/Software:
Siemens - Desigo PXC4 version All versions < V02.20.142.10-10884
- Affected Vendor/Software:
Siemens - Desigo PXC5 version All versions < V02.20.142.10-10884
CVSS3 Score: 9 - CRITICAL
Attack Vector ⓘ |
Attack Complexity |
Privileges Required |
User Interaction |
---|---|---|---|
NETWORK | LOW | LOW | REQUIRED |
Scope | Confidentiality Impact |
Integrity Impact |
Availability Impact |
CHANGED | HIGH | HIGH | HIGH |
CVSS2 Score: 8.5 - HIGH
Access Vector ⓘ |
Access Complexity |
Authentication |
---|---|---|
NETWORK | MEDIUM | SINGLE |
Confidentiality Impact |
Integrity Impact |
Availability Impact |
COMPLETE | COMPLETE | COMPLETE |
CVE References
Description | Tags ⓘ | Link |
---|---|---|
cert-portal.siemens.com application/pdf |
![]() |
Related QID Numbers
- 590968 Siemens Desigo PXC and DXR Devices (Update A) Multiple Vulnerabilities (ICSA-22-132-10) (ssa-662649) (ssa-626968)
Exploit/POC from Github
This repository contains a collection of data files on known Common Vulnerabilities and Exposures (CVEs). Each file i…
Known Affected Configurations (CPE V2.3)
Type | Vendor | Product | Version | Update | Edition | Language |
---|---|---|---|---|---|---|
Hardware
| Siemens | Desigo Pxc4 | - | All | All | All |
Operating System | Siemens | Desigo Pxc4 Firmware | All | All | All | All |
Hardware
| Siemens | Desigo Pxc5 | - | All | All | All |
Operating System | Siemens | Desigo Pxc5 Firmware | All | All | All | All |
- cpe:2.3:h:siemens:desigo_pxc4:-:*:*:*:*:*:*:*:
- cpe:2.3:o:siemens:desigo_pxc4_firmware:*:*:*:*:*:*:*:*:
- cpe:2.3:h:siemens:desigo_pxc5:-:*:*:*:*:*:*:*:
- cpe:2.3:o:siemens:desigo_pxc5_firmware:*:*:*:*:*:*:*:*:
Social Mentions
Source | Title | Posted (UTC) |
---|---|---|
![]() |
CVE-2022-24039 : A vulnerability has been identified in Desigo PXC4 All versions < V02.20.142.10-10884 , Desigo PX… twitter.com/i/web/status/1… | 2022-05-10 11:07:01 |
![]() |
CVE-2022-24039 | 2022-05-10 11:38:25 |