CVE-2022-30319
Summary
| CVE | CVE-2022-30319 |
|---|---|
| State | PUBLIC |
| Assigner | [email protected] |
| Source Priority | CVE Program / NVD first with legacy fallback |
| Published | 2022-07-28 16:15:00 UTC |
| Updated | 2023-08-08 14:21:00 UTC |
| Description | Saia Burgess Controls (SBC) PCD through 2022-05-06 allows Authentication bypass. According to FSCT-2022-0062, there is a Saia Burgess Controls (SBC) PCD S-Bus authentication bypass issue. The affected components are characterized as: S-Bus (5050/UDP) authentication. The potential impact is: Authentication bypass. The Saia Burgess Controls (SBC) PCD controllers utilize the S-Bus protocol (5050/UDP) for a variety of engineering purposes. It is possible to configure a password in order to restrict access to sensitive engineering functionality. Authentication functions on the basis of a MAC/IP whitelist with inactivity timeout to which an authenticated client's MAC/IP is stored. UDP traffic can be spoofed to bypass the whitelist-based access control. Since UDP is stateless, an attacker capable of passively observing traffic can spoof arbitrary messages using the MAC/IP of an authenticated client. This allows the attacker access to sensitive engineering functionality such as uploading/downloading control logic and manipulating controller configuration. |
Risk And Classification
Problem Types: CWE-290
NVD Known Affected Configurations (CPE 2.3)
| Type | Vendor | Product | Version | Update | Edition | Language |
|---|---|---|---|---|---|---|
| Application | Honeywell | Saia Pg5 Controls Suite | - | All | All | All |
References
| Reference | Source | Link | Tags |
|---|---|---|---|
| Honeywell Saia Burgess PG5 PCD | CISA | MISC | www.cisa.gov | |
| Blog - Forescout | MISC | www.forescout.com | |
| CVE Program record | CVE.ORG | www.cve.org | canonical |
| NVD vulnerability detail | NVD | nvd.nist.gov | canonical, analysis |
No vendor comments have been submitted for this CVE.
There are currently no legacy QID mappings associated with this CVE.