CVE-2025-40944
Summary
| CVE | CVE-2025-40944 |
|---|---|
| State | PUBLISHED |
| Assigner | siemens |
| Source Priority | CVE Program / NVD first with legacy fallback |
| Published | 2026-01-13 10:15:58 UTC |
| Updated | 2026-06-09 10:16:37 UTC |
| Description | A vulnerability has been identified in SIMATIC ET 200AL IM 157-1 PN (6ES7157-1AB00-0AB0) (All versions), SIMATIC ET 200MP IM 155-5 PN HF (6ES7155-5AA00-0AC0) (All versions >= V4.2.0), SIMATIC ET 200SP IM 155-6 MF HF (6ES7155-6MU00-0CN0) (All versions), SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants) (All versions < V1.3), SIMATIC ET 200SP IM 155-6 PN R1 (6ES7155-6AU00-0HM0) (All versions < V6.0.1), SIMATIC ET 200SP IM 155-6 PN/2 HF (6ES7155-6AU01-0CN0) (All versions >= V4.2.0 < V4.2.5), SIMATIC ET 200SP IM 155-6 PN/3 HF (6ES7155-6AU30-0CN0) (All versions < V4.2.2), SIMATIC PN/MF Coupler (6ES7158-3MU10-0XA0) (All versions), SIMATIC PN/PN Coupler (6ES7158-3AD10-0XA0) (All versions < V6.0.0), SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-2AC0) (All versions >= V4.2.0), SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-7AC0) (All versions >= V4.2.0), SIPLUS ET 200MP IM 155-5 PN HF T1 RAIL (6AG2155-5AA00-1AC0) (All versions >= V4.2.0), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-2CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-7CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF T1 RAIL (6AG2155-6AU01-1CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF TX RAIL (6AG2155-6AU01-4CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS NET PN/PN Coupler (6AG2158-3AD10-4XA0) (All versions < V6.0.0). Affected devices do not properly handle S7 protocol session disconnect requests. When receiving a valid S7 protocol Disconnect Request (COTP DR TPDU) on TCP port 102, the devices enter an improper session state. This could allow an attacker to cause the device to become unresponsive, leading to a denial-of-service condition that requires a power cycle to restore normal operation. |
Risk And Classification
Primary CVSS: v4.0 8.7 HIGH from [email protected]
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X
EPSS: 0.000150000 probability, percentile 0.033990000 (date 2026-06-13)
Problem Types: CWE-400 | CWE-400 CWE-400: Uncontrolled Resource Consumption
| Version | Source | Type | Score | Severity | Vector |
|---|---|---|---|---|---|
| 4.0 | [email protected] | Secondary | 8.7 | HIGH | CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N/E:X/C... |
| 4.0 | CNA | DECLARED | 8.7 | HIGH | CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N |
| 3.1 | [email protected] | Secondary | 7.5 | HIGH | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H |
| 3.1 | CNA | DECLARED | 7.5 | HIGH | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H |
CVSS v4.0 Breakdown
Attack Vector
NetworkAttack Complexity
LowAttack Requirements
NonePrivileges Required
NoneUser Interaction
NoneConfidentiality
NoneIntegrity
NoneAvailability
HighSub Conf.
NoneSub Integrity
NoneSub Availability
NoneCVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X
CVSS v3.1 Breakdown
Attack Vector
NetworkAttack Complexity
LowPrivileges Required
NoneUser Interaction
NoneScope
UnchangedConfidentiality
NoneIntegrity
NoneAvailability
HighCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
Vendor Declared Affected Products
| Source | Vendor | Product | Version | Platforms |
|---|---|---|---|---|
| CNA | Siemens | SIMATIC ET 200AL IM 157-1 PN | affected * custom | Not specified |
| CNA | Siemens | SIMATIC ET 200MP IM 155-5 PN HF | affected V4.2.0 * custom | Not specified |
| CNA | Siemens | SIMATIC ET 200SP IM 155-6 MF HF | affected * custom | Not specified |
| CNA | Siemens | SIMATIC ET 200SP IM 155-6 PN HA Incl. SIPLUS Variants | affected V1.3 custom | Not specified |
| CNA | Siemens | SIMATIC ET 200SP IM 155-6 PN R1 | affected V6.0.1 custom | Not specified |
| CNA | Siemens | SIMATIC ET 200SP IM 155-6 PN/2 HF | affected V4.2.0 V4.2.5 custom | Not specified |
| CNA | Siemens | SIMATIC ET 200SP IM 155-6 PN/3 HF | affected V4.2.2 custom | Not specified |
| CNA | Siemens | SIMATIC PN/MF Coupler | affected * custom | Not specified |
| CNA | Siemens | SIMATIC PN/PN Coupler | affected V6.0.0 custom | Not specified |
| CNA | Siemens | SIPLUS ET 200MP IM 155-5 PN HF | affected V4.2.0 * custom | Not specified |
| CNA | Siemens | SIPLUS ET 200MP IM 155-5 PN HF | affected V4.2.0 * custom | Not specified |
| CNA | Siemens | SIPLUS ET 200MP IM 155-5 PN HF T1 RAIL | affected V4.2.0 * custom | Not specified |
| CNA | Siemens | SIPLUS ET 200SP IM 155-6 PN HF | affected V4.2.0 V4.2.5 custom | Not specified |
| CNA | Siemens | SIPLUS ET 200SP IM 155-6 PN HF | affected V4.2.0 V4.2.5 custom | Not specified |
| CNA | Siemens | SIPLUS ET 200SP IM 155-6 PN HF T1 RAIL | affected V4.2.0 V4.2.5 custom | Not specified |
| CNA | Siemens | SIPLUS ET 200SP IM 155-6 PN HF TX RAIL | affected V4.2.0 V4.2.5 custom | Not specified |
| CNA | Siemens | SIPLUS NET PN/PN Coupler | affected V6.0.0 custom | Not specified |
References
| Reference | Source | Link | Tags |
|---|---|---|---|
| cert-portal.siemens.com/productcert/html/ssa-674753.html | [email protected] | cert-portal.siemens.com | |
| CVE Program record | CVE.ORG | www.cve.org | canonical |
| NVD vulnerability detail | NVD | nvd.nist.gov | canonical, analysis |
No vendor comments have been submitted for this CVE.
There are currently no legacy QID mappings associated with this CVE.