Stack-based buffer overflow in Danfoss AK-SM8xxA unauthenticated CGI handler
Summary
| CVE | CVE-2026-129713 |
|---|---|
| State | PUBLISHED |
| Assigner | Danfoss |
| Source Priority | CVE Program / NVD first with legacy fallback |
| Published | 2026-11-20 11:18:30 UTC |
| Updated | 2026-11-24 17:50:07 UTC |
| Description | A stack-based buffer overflow in an unauthenticated CGI handler of the Danfoss AK-SM 8xxA Series controller allows remote attackers to send specially crafted HTTP/S POST requests, leading to memory corruption, webserver restart and hypothetically potential arbitrary code execution with webserver privileges. Authentication is not required to exploit this vulnerability. |
Risk And Classification
Primary CVSS: v4.0 9.3 CRITICAL from d7ff35af-cf88-454c-bab9-af60602f10f8
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X
EPSS: 0.009640000 probability, percentile 0.625420000 (date 2026-11-22)
Problem Types: CWE-121 | CWE-121 CWE-121 Stack-based buffer overflow
| Version | Source | Type | Score | Severity | Vector |
|---|---|---|---|---|---|
| 4.0 | d7ff35af-cf88-454c-bab9-af60602f10f8 | Secondary | 9.3 | CRITICAL | CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/C... |
| 4.0 | CNA | CVSS | 9.3 | CRITICAL | CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N |
CVSS v4.0 Breakdown
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X
Vendor Declared Affected Products
References
| Reference | Source | Link | Tags |
|---|---|---|---|
| www.danfoss.com/en/service-and-support/coordinated-vulnerability-disclosure/d... | d7ff35af-cf88-454c-bab9-af60602f10f8 | www.danfoss.com | |
| CVE Program record | CVE.ORG | www.cve.org | canonical |
| NVD vulnerability detail | NVD | nvd.nist.gov | canonical, analysis |
Additional Advisory Data
Solutions
CNA: * This vulnerability will be addressed in Danfoss AK-SM 8xxA Series upcoming software version 5.5.x. * Further, we will remove the option that customers can disable the product Strict mode.
Workarounds
CNA: * Follow the instructions provided in the product’s manual, avoiding Internet exposure of all units on public IP * Make sure remote access to the units is possible only through a secure VPN or in general over a protected network * Configure the units to Strict mode, which ensures higher security levels on the product * Recommend using strong passwords