Tycon Systems TPDIN-Monitor-WEB2 Missing Authentication for Critical Function
Summary
| CVE | CVE-2026-61884 |
|---|---|
| State | PUBLISHED |
| Assigner | icscert |
| Source Priority | CVE Program / NVD first with legacy fallback |
| Published | 2026-07-24 22:16:50 UTC |
| Updated | 2026-09-04 22:17:17 UTC |
| Description | The Tycon Systems TPDIN-Monitor-WEB2 ships without HTTP credentials configured, intended for an installer to set them on first use. On firmware 2.4.4 and earlier, a unit left in this unconfigured state serves the web management interface without requiring any login. An attacker with network access to such a unit can reach full device controls, including power relay management, device reboot, remote access service configuration, and network settings, which could allow disruption of connected infrastructure or physical damage to equipment. |
Risk And Classification
Primary CVSS: v4.0 9.3 CRITICAL from [email protected]
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X
EPSS: 0.004480000 probability, percentile 0.375420000 (date 2026-09-07)
Problem Types: CWE-306 | CWE-306 CWE-306
| Version | Source | Type | Score | Severity | Vector |
|---|---|---|---|---|---|
| 4.0 | [email protected] | Secondary | 9.3 | CRITICAL | CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/C... |
| 4.0 | CNA | CVSS | 9.3 | CRITICAL | CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N |
| 3.1 | [email protected] | Secondary | 9.8 | CRITICAL | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H |
| 3.1 | CNA | CVSS | 9.8 | CRITICAL | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H |
CVSS v4.0 Breakdown
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X
CVSS v3.1 Breakdown
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Vendor Declared Affected Products
| Source | Vendor | Product | Version | Platforms |
|---|---|---|---|---|
| CNA | Tycon Systems | TPDIN-Monitor-WEB2 | affected 2.4.5 custom | Not specified |
| CNA | Tycon Systems | TPDIN-Monitor-WEB2 | unaffected 2.4.5 | Not specified |
References
| Reference | Source | Link | Tags |
|---|---|---|---|
| www.cisa.gov/news-events/ics-advisories/icsa-26-202-01 | [email protected] | www.cisa.gov | |
| github.com/cisagov/CSAF/blob/develop/csaf_files/OT/white/2026/icsa-26-20... | [email protected] | github.com | |
| www.tyconsystems.com/contact | MITRE | www.tyconsystems.com | |
| CVE Program record | CVE.ORG | www.cve.org | canonical |
| NVD vulnerability detail | NVD | nvd.nist.gov | canonical, analysis |
Vendor Comments And Credit
Discovery Credit
CNA: Abdiwelli Guled reported this vulnerability to CISA. (en)
Additional Advisory Data
Solutions
CNA: Tycon Systems has released firmware 2.4.5, which resolves this vulnerability by requiring an administrator username and password to be set before the web interface is served. Further inquiries can be directed to [email protected]. Tycon Systems recommends setting an administrative username and strong password on the Network Configuration page and confirming in a private browser window that a login is required, for units still running firmware 2.4.4 or earlier. Repeat this after any factory reset. Tycon Systems recommends not exposing the web interface to the Internet, as it is HTTP only. The unit should be kept on a private network, behind a firewall or VPN.