{"api_version":"1","generated_at":"2026-07-23T19:17:40+00:00","cve":"CVE-2022-24045","urls":{"html":"https://cve.report/CVE-2022-24045","api":"https://cve.report/api/cve/CVE-2022-24045.json","docs":"https://cve.report/api","cve_org":"https://www.cve.org/CVERecord?id=CVE-2022-24045","nvd":"https://nvd.nist.gov/vuln/detail/CVE-2022-24045"},"summary":{"title":"CVE-2022-24045","description":"A vulnerability has been identified in Desigo DXR2 (All versions < V01.21.142.5-22), Desigo PXC3 (All versions < V01.21.142.4-18), Desigo PXC4 (All versions < V02.20.142.10-10884), Desigo PXC5 (All versions < V02.20.142.10-10884). The application, after a successful login, sets the session cookie on the browser via client-side JavaScript code, without applying any security attributes (such as “Secure”, “HttpOnly”, or “SameSite”). Any attempts to browse the application via unencrypted HTTP protocol would lead to the transmission of all his/her session cookies in plaintext through the network. An attacker could then be able to sniff the network and capture sensitive information.","state":"PUBLIC","assigner":"productcert@siemens.com","published_at":"2022-05-20 13:15:00","updated_at":"2023-06-23 19:48:00"},"problem_types":["NVD-CWE-Other","CWE-311"],"metrics":[],"references":[{"url":"https://cert-portal.siemens.com/productcert/pdf/ssa-626968.pdf","name":"N/A","refsource":"CONFIRM","tags":[],"title":"","mime":"application/pdf","httpstatus":"200","archivestatus":"200"},{"url":"https://www.cve.org/CVERecord?id=CVE-2022-24045","name":"CVE Program record","refsource":"CVE.ORG","tags":["canonical"]},{"url":"https://nvd.nist.gov/vuln/detail/CVE-2022-24045","name":"NVD vulnerability detail","refsource":"NVD","tags":["canonical","analysis"]}],"affected":[],"timeline":[],"solutions":[],"workarounds":[],"exploits":[],"credits":[],"nvd_cpes":[{"cve_year":"2022","cve_id":"24045","vulnerable":"-1","versionEndIncluding":"","cpe1":"cpe","cpe2":"2.3","cpe3":"h","cpe4":"siemens","cpe5":"desigo_dxr2","cpe6":"-","cpe7":"*","cpe8":"*","cpe9":"*","cpe10":"*","cpe11":"*","cpe12":"*","cpe13":"*"},{"cve_year":"2022","cve_id":"24045","vulnerable":"1","versionEndIncluding":"","cpe1":"cpe","cpe2":"2.3","cpe3":"o","cpe4":"siemens","cpe5":"desigo_dxr2_firmware","cpe6":"*","cpe7":"*","cpe8":"*","cpe9":"*","cpe10":"*","cpe11":"*","cpe12":"*","cpe13":"*"},{"cve_year":"2022","cve_id":"24045","vulnerable":"-1","versionEndIncluding":"","cpe1":"cpe","cpe2":"2.3","cpe3":"h","cpe4":"siemens","cpe5":"desigo_pxc3","cpe6":"-","cpe7":"*","cpe8":"*","cpe9":"*","cpe10":"*","cpe11":"*","cpe12":"*","cpe13":"*"},{"cve_year":"2022","cve_id":"24045","vulnerable":"1","versionEndIncluding":"","cpe1":"cpe","cpe2":"2.3","cpe3":"o","cpe4":"siemens","cpe5":"desigo_pxc3_firmware","cpe6":"*","cpe7":"*","cpe8":"*","cpe9":"*","cpe10":"*","cpe11":"*","cpe12":"*","cpe13":"*"},{"cve_year":"2022","cve_id":"24045","vulnerable":"-1","versionEndIncluding":"","cpe1":"cpe","cpe2":"2.3","cpe3":"h","cpe4":"siemens","cpe5":"desigo_pxc4","cpe6":"-","cpe7":"*","cpe8":"*","cpe9":"*","cpe10":"*","cpe11":"*","cpe12":"*","cpe13":"*"},{"cve_year":"2022","cve_id":"24045","vulnerable":"1","versionEndIncluding":"","cpe1":"cpe","cpe2":"2.3","cpe3":"o","cpe4":"siemens","cpe5":"desigo_pxc4_firmware","cpe6":"*","cpe7":"*","cpe8":"*","cpe9":"*","cpe10":"*","cpe11":"*","cpe12":"*","cpe13":"*"},{"cve_year":"2022","cve_id":"24045","vulnerable":"-1","versionEndIncluding":"","cpe1":"cpe","cpe2":"2.3","cpe3":"h","cpe4":"siemens","cpe5":"desigo_pxc5","cpe6":"-","cpe7":"*","cpe8":"*","cpe9":"*","cpe10":"*","cpe11":"*","cpe12":"*","cpe13":"*"},{"cve_year":"2022","cve_id":"24045","vulnerable":"1","versionEndIncluding":"","cpe1":"cpe","cpe2":"2.3","cpe3":"o","cpe4":"siemens","cpe5":"desigo_pxc5_firmware","cpe6":"*","cpe7":"*","cpe8":"*","cpe9":"*","cpe10":"*","cpe11":"*","cpe12":"*","cpe13":"*"}],"vendor_comments":[],"enrichments":{"kev":null,"epss":null,"legacy_qids":[{"cve":"CVE-2022-24045","qid":"590968","title":"Siemens Desigo PXC and DXR Devices (Update A) Multiple Vulnerabilities (ICSA-22-132-10) (ssa-662649) (ssa-626968)"}]},"source_records":{"cve_program":{"CVE_data_meta":{"ASSIGNER":"productcert@siemens.com","ID":"CVE-2022-24045","STATE":"PUBLIC"},"data_format":"MITRE","data_version":"4.0","data_type":"CVE","affects":{"vendor":{"vendor_data":[{"vendor_name":"Siemens","product":{"product_data":[{"product_name":"Desigo DXR2","version":{"version_data":[{"version_value":"All versions < V01.21.142.5-22"}]}},{"product_name":"Desigo PXC3","version":{"version_data":[{"version_value":"All versions < V01.21.142.4-18"}]}},{"product_name":"Desigo PXC4","version":{"version_data":[{"version_value":"All versions < V02.20.142.10-10884"}]}},{"product_name":"Desigo PXC5","version":{"version_data":[{"version_value":"All versions < V02.20.142.10-10884"}]}}]}}]}},"problemtype":{"problemtype_data":[{"description":[{"lang":"eng","value":"CWE-614: Sensitive Cookie in HTTPS Session Without 'Secure' Attribute"}]}]},"description":{"description_data":[{"lang":"eng","value":"A vulnerability has been identified in Desigo DXR2 (All versions < V01.21.142.5-22), Desigo PXC3 (All versions < V01.21.142.4-18), Desigo PXC4 (All versions < V02.20.142.10-10884), Desigo PXC5 (All versions < V02.20.142.10-10884). The application, after a successful login, sets the session cookie on the browser via client-side JavaScript code, without applying any security attributes (such as “Secure”, “HttpOnly”, or “SameSite”). Any attempts to browse the application via unencrypted HTTP protocol would lead to the transmission of all his/her session cookies in plaintext through the network. An attacker could then be able to sniff the network and capture sensitive information."}]},"references":{"reference_data":[{"refsource":"MISC","url":"https://cert-portal.siemens.com/productcert/pdf/ssa-626968.pdf","name":"https://cert-portal.siemens.com/productcert/pdf/ssa-626968.pdf"}]}},"nvd":{"publishedDate":"2022-05-20 13:15:00","lastModifiedDate":"2023-06-23 19:48:00","problem_types":["NVD-CWE-Other","CWE-311"],"metrics":{"baseMetricV3":{"cvssV3":{"version":"3.1","vectorString":"CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N","attackVector":"NETWORK","attackComplexity":"LOW","privilegesRequired":"LOW","userInteraction":"NONE","scope":"UNCHANGED","confidentialityImpact":"HIGH","integrityImpact":"NONE","availabilityImpact":"NONE","baseScore":6.5,"baseSeverity":"MEDIUM"},"exploitabilityScore":2.8,"impactScore":3.6},"baseMetricV2":{"cvssV2":{"version":"2.0","vectorString":"AV:N/AC:L/Au:S/C:P/I:N/A:N","accessVector":"NETWORK","accessComplexity":"LOW","authentication":"SINGLE","confidentialityImpact":"PARTIAL","integrityImpact":"NONE","availabilityImpact":"NONE","baseScore":4},"severity":"MEDIUM","exploitabilityScore":8,"impactScore":2.9,"acInsufInfo":false,"obtainAllPrivilege":false,"obtainUserPrivilege":false,"obtainOtherPrivilege":false,"userInteractionRequired":false}},"configurations":{"CVE_data_version":"4.0","nodes":[{"operator":"AND","children":[{"operator":"OR","children":[],"cpe_match":[{"vulnerable":true,"cpe23Uri":"cpe:2.3:o:siemens:desigo_dxr2_firmware:*:*:*:*:*:*:*:*","versionEndExcluding":"01.21.142.5-22","cpe_name":[]}]},{"operator":"OR","children":[],"cpe_match":[{"vulnerable":false,"cpe23Uri":"cpe:2.3:h:siemens:desigo_dxr2:-:*:*:*:*:*:*:*","cpe_name":[]}]}],"cpe_match":[]},{"operator":"AND","children":[{"operator":"OR","children":[],"cpe_match":[{"vulnerable":true,"cpe23Uri":"cpe:2.3:o:siemens:desigo_pxc3_firmware:*:*:*:*:*:*:*:*","versionEndExcluding":"01.21.142.4-18","cpe_name":[]}]},{"operator":"OR","children":[],"cpe_match":[{"vulnerable":false,"cpe23Uri":"cpe:2.3:h:siemens:desigo_pxc3:-:*:*:*:*:*:*:*","cpe_name":[]}]}],"cpe_match":[]},{"operator":"AND","children":[{"operator":"OR","children":[],"cpe_match":[{"vulnerable":true,"cpe23Uri":"cpe:2.3:o:siemens:desigo_pxc4_firmware:*:*:*:*:*:*:*:*","versionEndExcluding":"02.20.142.10-10884","cpe_name":[]}]},{"operator":"OR","children":[],"cpe_match":[{"vulnerable":false,"cpe23Uri":"cpe:2.3:h:siemens:desigo_pxc4:-:*:*:*:*:*:*:*","cpe_name":[]}]}],"cpe_match":[]},{"operator":"AND","children":[{"operator":"OR","children":[],"cpe_match":[{"vulnerable":true,"cpe23Uri":"cpe:2.3:o:siemens:desigo_pxc5_firmware:*:*:*:*:*:*:*:*","versionEndExcluding":"02.20.142.10-10884","cpe_name":[]}]},{"operator":"OR","children":[],"cpe_match":[{"vulnerable":false,"cpe23Uri":"cpe:2.3:h:siemens:desigo_pxc5:-:*:*:*:*:*:*:*","cpe_name":[]}]}],"cpe_match":[]}]}},"legacy_mitre":{"record":{"CveYear":"2022","CveId":"24045","Ordinal":"227251","Title":"CVE-2022-24045","CVE":"CVE-2022-24045","Year":"2022"},"notes":[{"CveYear":"2022","CveId":"24045","Ordinal":"1","NoteData":"** RESERVED ** This candidate has been reserved by an organization or individual that will use it when announcing a new security problem. When the candidate has been publicized, the details for this candidate will be provided.","Type":"Description","Title":null}]}}}