{"api_version":"1","generated_at":"2026-10-25T06:32:23+00:00","cve":"CVE-2025-54849","urls":{"html":"https://cve.report/CVE-2025-54849","api":"https://cve.report/api/cve/CVE-2025-54849.json","docs":"https://cve.report/api","cve_org":"https://www.cve.org/CVERecord?id=CVE-2025-54849","nvd":"https://nvd.nist.gov/vuln/detail/CVE-2025-54849"},"summary":{"title":"CVE-2025-54849","description":"A denial of service vulnerability exists in the Modbus TCP and Modbus RTU over TCP functionality of Socomec DIRIS Digiware M-70 1.6.9. A specially crafted series of network requests can lead to a denial of service. An attacker can send a sequence of unauthenticated packets to trigger this vulnerability.An attacker can trigger this denial-of-service condition by sending a single Modbus TCP message to port 502 using the Write Single Register function code (6) to write the value 1 to register 4352. This action changes the Modbus address to 15. After this message is sent, the device will be in a denial-of-service state.","state":"PUBLISHED","assigner":"talos","published_at":"2025-12-01 16:15:53","updated_at":"2026-09-26 00:10:00"},"problem_types":["CWE-306","CWE-306 CWE-306: Missing Authentication for Critical Function"],"metrics":[{"version":"3.1","source":"talos-cna@cisco.com","type":"Secondary","score":"7.5","severity":"HIGH","vector":"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H","data":{"version":"3.1","vectorString":"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H","baseScore":7.5,"baseSeverity":"HIGH","attackVector":"NETWORK","attackComplexity":"LOW","privilegesRequired":"NONE","userInteraction":"NONE","scope":"UNCHANGED","confidentialityImpact":"NONE","integrityImpact":"NONE","availabilityImpact":"HIGH"}},{"version":"3.1","source":"CNA","type":"DECLARED","score":"7.5","severity":"HIGH","vector":"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H","data":{"attackComplexity":"LOW","attackVector":"NETWORK","availabilityImpact":"HIGH","baseScore":7.5,"baseSeverity":"HIGH","confidentialityImpact":"NONE","integrityImpact":"NONE","privilegesRequired":"NONE","scope":"UNCHANGED","userInteraction":"NONE","vectorString":"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H","version":"3.1"}}],"references":[{"url":"https://talosintelligence.com/vulnerability_reports/TALOS-2025-2248","name":"https://talosintelligence.com/vulnerability_reports/TALOS-2025-2248","refsource":"talos-cna@cisco.com","tags":["Vendor Advisory"],"title":"","mime":"","httpstatus":"","archivestatus":"0"},{"url":"https://www.cve.org/CVERecord?id=CVE-2025-54849","name":"CVE Program record","refsource":"CVE.ORG","tags":["canonical"]},{"url":"https://nvd.nist.gov/vuln/detail/CVE-2025-54849","name":"NVD vulnerability detail","refsource":"NVD","tags":["canonical","analysis"]}],"affected":[{"source":"CNA","vendor":"Socomec","product":"DIRIS Digiware M-70","version":"affected 1.6.9","platforms":[]}],"timeline":[],"solutions":[],"workarounds":[],"exploits":[],"credits":[{"source":"CNA","value":"Discovered by Kelly Patterson of Cisco Talos.","lang":"en"}],"nvd_cpes":[{"cve_year":"2025","cve_id":"54849","vulnerable":"0","versionEndIncluding":"","cpe1":"cpe","cpe2":"2.3","cpe3":"h","cpe4":"socomec","cpe5":"diris_digiware_m-70","cpe6":"-","cpe7":"*","cpe8":"*","cpe9":"*","cpe10":"*","cpe11":"*","cpe12":"*","cpe13":"*"},{"cve_year":"2025","cve_id":"54849","vulnerable":"1","versionEndIncluding":"","cpe1":"cpe","cpe2":"2.3","cpe3":"o","cpe4":"socomec","cpe5":"diris_digiware_m-70_firmware","cpe6":"1.6.9","cpe7":"*","cpe8":"*","cpe9":"*","cpe10":"*","cpe11":"*","cpe12":"*","cpe13":"*"}],"vendor_comments":[],"enrichments":{"kev":null,"epss":{"cve_year":"2025","cve_id":"54849","cve":"CVE-2025-54849","epss":"0.003210000","percentile":"0.226550000","score_date":"2026-09-27","updated_at":"2026-09-28 00:02:20"},"legacy_qids":[]},"source_records":{"cve_program":{"containers":{"adp":[{"metrics":[{"other":{"content":{"id":"CVE-2025-54849","options":[{"Exploitation":"none"},{"Automatable":"no"},{"Technical Impact":"partial"}],"role":"CISA Coordinator","timestamp":"2025-12-01T20:16:17.676904Z","version":"2.0.3"},"type":"ssvc"}}],"providerMetadata":{"dateUpdated":"2025-12-01T20:16:27.906Z","orgId":"134c704f-9b21-4f2e-91b3-4a467353bcc0","shortName":"CISA-ADP"},"title":"CISA ADP Vulnrichment"}],"cna":{"affected":[{"product":"DIRIS Digiware M-70","vendor":"Socomec","versions":[{"status":"affected","version":"1.6.9"}]}],"credits":[{"lang":"en","value":"Discovered by Kelly Patterson of Cisco Talos."}],"descriptions":[{"lang":"en","value":"A denial of service vulnerability exists in the Modbus TCP and Modbus RTU over TCP functionality of Socomec DIRIS Digiware M-70 1.6.9. A specially crafted series of network requests can lead to a denial of service. An attacker can send a sequence of unauthenticated packets to trigger this vulnerability.An attacker can trigger this denial-of-service condition by sending a single Modbus TCP message to port 502 using the Write Single Register function code (6) to write the value 1 to register 4352. This action changes the Modbus address to 15. After this message is sent, the device will be in a denial-of-service state."}],"metrics":[{"cvssV3_1":{"attackComplexity":"LOW","attackVector":"NETWORK","availabilityImpact":"HIGH","baseScore":7.5,"baseSeverity":"HIGH","confidentialityImpact":"NONE","integrityImpact":"NONE","privilegesRequired":"NONE","scope":"UNCHANGED","userInteraction":"NONE","vectorString":"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H","version":"3.1"}}],"problemTypes":[{"descriptions":[{"cweId":"CWE-306","description":"CWE-306: Missing Authentication for Critical Function","lang":"en","type":"CWE"}]}],"providerMetadata":{"dateUpdated":"2025-12-01T15:25:13.025Z","orgId":"b86d76f8-0f8a-4a96-a78d-d8abfc7fc29b","shortName":"talos"},"references":[{"name":"https://talosintelligence.com/vulnerability_reports/TALOS-2025-2248","url":"https://talosintelligence.com/vulnerability_reports/TALOS-2025-2248"}]}},"cveMetadata":{"assignerOrgId":"b86d76f8-0f8a-4a96-a78d-d8abfc7fc29b","assignerShortName":"talos","cveId":"CVE-2025-54849","datePublished":"2025-12-01T15:25:13.025Z","dateReserved":"2025-07-31T15:17:58.545Z","dateUpdated":"2025-12-01T20:16:27.906Z","state":"PUBLISHED"},"dataType":"CVE_RECORD","dataVersion":"5.2"},"nvd":{"publishedDate":"2025-12-01 16:15:53","lastModifiedDate":"2026-09-26 00:10:00","problem_types":["CWE-306","CWE-306 CWE-306: Missing Authentication for Critical Function"],"metrics":{"cvssMetricV31":[{"source":"talos-cna@cisco.com","type":"Secondary","cvssData":{"version":"3.1","vectorString":"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H","baseScore":7.5,"baseSeverity":"HIGH","attackVector":"NETWORK","attackComplexity":"LOW","privilegesRequired":"NONE","userInteraction":"NONE","scope":"UNCHANGED","confidentialityImpact":"NONE","integrityImpact":"NONE","availabilityImpact":"HIGH"},"exploitabilityScore":3.9,"impactScore":3.6}],"ssvcV203":[{"source":"134c704f-9b21-4f2e-91b3-4a467353bcc0","ssvcData":{"timestamp":"2025-12-01T20:16:17.676904Z","id":"CVE-2025-54849","options":[{"exploitation":"none"},{"automatable":"no"},{"technicalImpact":"partial"}],"role":"CISA Coordinator","version":"2.0.3"}}]},"configurations":[{"operator":"AND","nodes":[{"operator":"OR","negate":false,"cpeMatch":[{"vulnerable":true,"criteria":"cpe:2.3:o:socomec:diris_digiware_m-70_firmware:1.6.9:*:*:*:*:*:*:*","matchCriteriaId":"741E83B6-F217-46E7-9E3A-8E446250C785"}]},{"operator":"OR","negate":false,"cpeMatch":[{"vulnerable":false,"criteria":"cpe:2.3:h:socomec:diris_digiware_m-70:-:*:*:*:*:*:*:*","matchCriteriaId":"76CAA8C6-29FD-40F3-9702-790CD73F3052"}]}]}]},"legacy_mitre":{"record":{"CveYear":"2025","CveId":"54849","Ordinal":"1","Title":"CVE-2025-54849","CVE":"CVE-2025-54849","Year":"2025"},"notes":[{"CveYear":"2025","CveId":"54849","Ordinal":"1","NoteData":"A denial of service vulnerability exists in the Modbus TCP and Modbus RTU over TCP functionality of Socomec DIRIS Digiware M-70 1.6.9. A specially crafted series of network requests can lead to a denial of service. An attacker can send a sequence of unauthenticated packets to trigger this vulnerability.An attacker can trigger this denial-of-service condition by sending a single Modbus TCP message to port 502 using the Write Single Register function code (6) to write the value 1 to register 4352. This action changes the Modbus address to 15. After this message is sent, the device will be in a denial-of-service state.","Type":"Description","Title":"CVE-2025-54849"}]}}}