DescriptionKNX devices that use KNX Connection Authorization and support Option 1 are, depending on the implementation, vulnerable to being locked and users being unable to reset them to gain access to the device. The BCU key feature on the devices can be used to create a password for the device, but this password can often not be reset without entering the current password. If the device is configured to interface with a network, an attacker with access to that network could interface with the KNX installation, purge all devices without additional security options enabled, and set a BCU key, locking the device. Even if a device is not connected to a network, an attacker with physical access to the device could also exploit this vulnerability in the same way.

Risk And Classification

Primary CVSS: v3.1 7.5 HIGH from [email protected]

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

EPSS: 0.008550000 probability, percentile 0.545440000 (date 2026-07-22)

CISA KEV: Listed on 2026-07-15; due 2026-07-29; ransomware use Unknown

Problem Types: CWE-645 | CWE-645 CWE-645 Overly Restrictive Account Lockout Mechanism


VersionSourceTypeScoreSeverityVector
3.1[email protected]Primary7.5HIGHCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
3.1[email protected]Secondary7.5HIGHCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
3.1CNACVSS7.5HIGHCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

CVSS v3.1 Breakdown

Attack Vector
Network
Attack Complexity
Low
Privileges Required
None
User Interaction
None
Scope
Unchanged
Confidentiality
None
Integrity
None
Availability
High

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

CISA Known Exploited Vulnerability

VendorKNX Association
ProductKNX Protocol Connection Authorization Option 1
NameKNX Association KNX Protocol Connection Authorization Option 1 Overly Restrictive Account Lockout Mechanism Vulnerability
Required ActionApply mitigations in accordance with vendor instructions, ensuring compliance with CISA’s BOD 26-04 Prioritizing Security Updates Based on Risk (see URL in Notes) guidance and CISA’s “Forensics Triage Requirements” (see URL in Notes). Follow applicable BOD 26-04 guidance for cloud services or discontinue use of the product if mitigations are unavailable. Stakeholders are responsible for evaluating each asset's internet exposure and ensuring adherence to BOD 26-04 patching guidelines.
Noteshttps://www.cisa.gov/news-events/ics-advisories/icsa-23-236-01 ; BOD 26-04: https://www.cisa.gov/news-events/directives/bod-26-04-prioritizing-security-updates-based-risk ; Forensics Triage Requirements: https://www.cisa.gov/news-events/directives/bod-26-04-implementation-guidance-prioritizing-security-updates-based-risk ; https://nvd.nist.gov/vuln/detail/CVE-2023-4346

NVD Known Affected Configurations (CPE 2.3)

TypeVendorProductVersionUpdateEditionLanguage
Application Knx Connection Authorization - All All All

Vendor Declared Affected Products

SourceVendorProductVersionPlatforms
CNA KNX Association KNX Protocol Connection Authorization Option 1 affected Not specified

References

ReferenceSourceLinkTags
www.cisa.gov/known-exploited-vulnerabilities-catalog 134c704f-9b21-4f2e-91b3-4a467353bcc0 www.cisa.gov US Government Resource
KNX Protocol | CISA af854a3a-2127-422b-91ae-364da2661108 www.cisa.gov Third Party Advisory, US Government Resource
CVE Program record CVE.ORG www.cve.org canonical
NVD vulnerability detail NVD nvd.nist.gov canonical, analysis
CISA Known Exploited Vulnerabilities catalog CISA www.cisa.gov kev

Vendor Comments And Credit

Discovery Credit

CNA: Felix Eberstaller (en)

CNA: Limes Security (en)

Additional Advisory Data

SourceTimeEvent
ADP2026-07-15T00:00:00.000ZCVE-2023-4346 added to CISA KEV

Workarounds

CNA: The KNX Association recommends users always set the BCU Key in every KNX Project that is already finished and will be commissioned in the future. Handover the BCU Key as part of the Project Documentation to the Building Owner.

© CVE.report 2026

Use of this information constitutes acceptance for use in an AS IS condition. There are NO warranties, implied or otherwise, with regard to this information or its use. Any use of this information is at the user's risk. It is the responsibility of user to evaluate the accuracy, completeness or usefulness of any information, opinion, advice or other content. EACH USER WILL BE SOLELY RESPONSIBLE FOR ANY consequences of his or her direct or indirect use of this web site. ALL WARRANTIES OF ANY KIND ARE EXPRESSLY DISCLAIMED. This site will NOT BE LIABLE FOR ANY DIRECT, INDIRECT or any other kind of loss.

CVE, CWE, and OVAL are registred trademarks of The MITRE Corporation and the authoritative source of CVE content is MITRE's CVE web site. This site includes MITRE data granted under the following license.

Free CVE JSON API cve.report/api

CVE.report and Source URL Uptime Status status.cve.report