Exploitation of Weak or Known Passwords in Danfoss AK-SC 355 and AK-SM 800 Series
Summary
| CVE | CVE-2026-127057 |
|---|---|
| State | PUBLISHED |
| Assigner | Danfoss |
| Source Priority | CVE Program / NVD first with legacy fallback |
| Published | 2026-11-20 11:18:30 UTC |
| Updated | 2026-11-24 17:50:07 UTC |
| Description | The Danfoss legacy AK-SC 355 and AK-SM 800 Series are vulnerable to unauthorized access when default credentials or known passwords are used for authentication. These products were manufactured with default credentials documented in the product manual. All versions are affected. |
Risk And Classification
Primary CVSS: v4.0 9.9 CRITICAL from d7ff35af-cf88-454c-bab9-af60602f10f8
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:L/SI:L/SA:H/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X
EPSS: 0.006860000 probability, percentile 0.536050000 (date 2026-11-22)
Problem Types: CWE-1392 | CWE-1392 CWE-1392 Use of default credentials
| Version | Source | Type | Score | Severity | Vector |
|---|---|---|---|---|---|
| 4.0 | d7ff35af-cf88-454c-bab9-af60602f10f8 | Secondary | 9.9 | CRITICAL | CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:L/SI:L/SA:H/E:X/C... |
| 4.0 | CNA | CVSS | 9.9 | CRITICAL | CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:L/SI:L/SA:H |
CVSS v4.0 Breakdown
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:L/SI:L/SA:H/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X
Vendor Declared Affected Products
References
| Reference | Source | Link | Tags |
|---|---|---|---|
| www.danfoss.com/en/service-and-support/coordinated-vulnerability-disclosure/d... | d7ff35af-cf88-454c-bab9-af60602f10f8 | www.danfoss.com | |
| CVE Program record | CVE.ORG | www.cve.org | canonical |
| NVD vulnerability detail | NVD | nvd.nist.gov | canonical, analysis |
Additional Advisory Data
Solutions
CNA: * Install according to the instructions of the manual, avoiding public IP exposure * Update the fleet (AK-SC355, AK-SM800) to current generation products (AK-SM800A series), to ensure receiving continuous cybersecurity updates.
Workarounds
CNA: * Remove internet exposure of affected units and of all units exposed on public IP * Recommend using strong and unique passwords * Re-establish access to the units only through a secure VPN or in general over a protected network