Red Lion Controls N-Tron 700 Series Missing Authentication for Critical Function
Summary
| CVE | CVE-2026-33367 |
|---|---|
| State | PUBLISHED |
| Assigner | icscert |
| Source Priority | CVE Program / NVD first with legacy fallback |
| Published | 2026-10-09 15:17:14 UTC |
| Updated | 2026-10-09 15:17:14 UTC |
| Description | SNMP can be used to perform administrative actions such as retrieving configuration files, modifying user accounts or device settings, and initiating firmware or bootloader upgrades or downgrades—all without any authentication. |
Risk And Classification
Primary CVSS: v4.0 9.3 CRITICAL from [email protected]
CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:N/SC:H/SI:H/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X
Problem Types: CWE-306 | CWE-306 CWE-306
| Version | Source | Type | Score | Severity | Vector |
|---|---|---|---|---|---|
| 4.0 | [email protected] | Secondary | 9.3 | CRITICAL | CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:N/SC:H/SI:H/SA:N/E:X/C... |
| 4.0 | CNA | CVSS | 9.3 | CRITICAL | CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:N/SC:H/SI:H/SA:N |
| 3.1 | [email protected] | Secondary | 8.1 | HIGH | CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:N |
| 3.1 | CNA | CVSS | 8.1 | HIGH | CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:N |
CVSS v4.0 Breakdown
CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:N/SC:H/SI:H/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X
CVSS v3.1 Breakdown
CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:N
Vendor Declared Affected Products
| Source | Vendor | Product | Version | Platforms |
|---|---|---|---|---|
| CNA | Red Lion Controls | 700 Series | affected Firmware Versions 3.11.0 custom | Not specified |
| CNA | Red Lion Controls | 700 Series | affected Bootloader Versions 2.0.6.1 custom | Not specified |
| CNA | Red Lion Controls | 700 Series | unaffected 3.11.1 | Not specified |
References
| Reference | Source | Link | Tags |
|---|---|---|---|
| www.hms-networks.com/cybersecurity | [email protected] | www.hms-networks.com | |
| www.hms-networks.com | [email protected] | www.hms-networks.com | |
| github.com/cisagov/CSAF/blob/develop/csaf_files/OT/white/2026/icsa-26-28... | [email protected] | github.com | |
| www.cisa.gov/news-events/ics-advisories/icsa-26-281-01 | [email protected] | www.cisa.gov | |
| CVE Program record | CVE.ORG | www.cve.org | canonical |
| NVD vulnerability detail | NVD | nvd.nist.gov | canonical, analysis |
Vendor Comments And Credit
Discovery Credit
CNA: Gabrianna (Ria) Milloway of Idaho National Laboratory reported this vulnerability to CISA. (en)
Additional Advisory Data
Solutions
CNA: Red Lion controls recommends the following upgrades for the N-Tron 700 Series: * Upgrade to firmware version 3.11.1 or greater * Configure or disable the SNMP communities * Disable access to the web GUI The upgrade procedure document can be viewed here https://www.hms-networks.com/ . The advisory issued by HMS Networks regarding these vulnerabilities can be viewed here https://www.hms-networks.com/cybersecurity .